Post Offer Free
Wugao HuaRui High voltage Technology Co.,Ltd.  

Gold Index: 5433

You are here: home  > AC-DC power supply test equipment (no PD test transformer)  > Series resonant frequency step-up device

Series resonant frequency step-up device 

Place of Origin: Hubei, China (Mainland) 
inquire
Add to My Favorites
HiSupplier Escrow
Share |

Product Detail

Model No.: HVYDXB
Delivery Date: 5
Production Capacity: 50
Brand Name: CNHV

1600kVA/800kV,2A Frequency of Non-Partial Discharge series resonant tone AC voltage high voltage test sets of devices.

 

.

One. Name and Type of equipment

HVYDXB(W)-1600kVA/800kV,2A Frequency of Non-Partial Discharge series resonant tone AC voltage high voltage test sets of devices.

Two. Usage.

For CT / VT / CVT (CT / PT / CVT) and other high-voltage electrical equipment partial discharge test and the AC voltage test, to meet the 500kV the CT / VT (PT) / CVT calibration of transformer, no local discharge test and the AC voltage withstand test. Single test sample relative to capacity 500~8800pF, the maximum test voltage of not more than 800kV.

Three. Working environment.

3.1 Environment temperature: -150C –+50 0C;

3.2 Relative Humidity: ≤95%RH;

3.3 Elevation height: ≤3500;

3.4 Non-conduct electricity dust;

3.5 Maximum daily temperature gap: 25℃

3.6 Atmospheric pressure: 0.1Mpa

3.7 Atmospheric humidity:11g/m3

3.8 Earthquake intensity: ≤7

3.9 The actual supply voltage sine wave, waveform distortion≤1%

3.10 There is a reliable grounding, grounding resistance<0.5?

3.11 No fire and explosion danger;

3.12 No Corrosion of metal and insulation presence of gas.

3.13 Use inside house,fixed.

3.14 Working frequency:50Hz

3.15 The entire package for the non-PD-type high voltage test equipment.

Four. Main functions.

4.1 Fixed capacity:1600 kVA;

4.2 Fixed input voltage:single voltage 380V,Frequency:50Hz;

4.3 The maximum fixed output voltage: 800kV;

4.4 The maximum fixed output current:AC 2A;

4.5 Fixed frequency:50Hz;

4.6 Waveform distortion rate: Output voltage waveform distortion ≤ 1%;

4.7 Work time:Fixed load allow continuous 30 minutes;over-voltage 1.1 times for one minute.

4.8 Temperature rose: continuous operation under rated load temperature rise after 30 minutes ≤ 50K;

4.9 Quality factors:equipment itself Q≥40(f=50Hz);

4.10 Conservation functions:has over current, over voltage and flashover protection of product has been tested;

4.11 Measuring accuracy: The system RMS AC 1.0%.

4.12 the whole device Partial discharge: 800kV under ≤ 10pC, 85% UH partial discharge under no content.

4.13 Noise level: ≤65db




Mr. YuHao
 Mr. YuHao
manager
Tel: 86-27-62697887
Fax: 86-27-62162884
Mobile: 131 6327 2010
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Related Products

Company Info

Wugao HuaRui High voltage Technology Co.,Ltd. [China (Mainland)]


Business Type:Manufacturer
City: Wuhan
Province/State: Hubei
Country/Region: China (Mainland)

You May Like: